Eaton Moeller® series Rapid Link - Speed controllers, 8.5 A, 4 kW, Sensor input 4, Actuator output 2, 400/480 V AC, PROFINET, HAN Q4/2, with manual override switch, with braking resistance, with fan
Product Name |
Eaton Rapid Link Speed controller
|
Catalog Number |
199051
|
EAN |
4015081971091
|
Product Length/Depth |
195 mm
|
Product Height |
270 mm
|
Product Width |
220 mm
|
Product Weight |
3.82 kg
|
Certifications |
UL 61800-5-1
UL approval CE IEC/EN 61800-5-1 RoHS |
Catalog Notes |
|
Model Code |
RASP5-8424PNT-412R101S1
|
Features |
Parameterization: drivesConnect
Parameterization: Fieldbus Parameterization: Keypad Internal and on heat sink, temperature-controlled Fan Parameterization: drivesConnect mobile (App) |
Fitted with: |
Selector switch (Positions: REV - OFF - FWD)
2 Actuator outputs IGBT inverter Key switch position HAND Control unit Fan Key switch position OFF/RESET Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation Braking resistance PTC thermistor monitoring PC connection Breaking resistance Key switch position AUTO Thermo-click with safe isolation Internal DC link Manual override switch |
Functions |
3 fixed speeds
1 potentiometer speed Brake chopper with braking resistance for dynamic braking 4-quadrant operation possible For actuation of motors with mechanical brake |
Degree of protection |
IP65
NEMA 12 |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Overvoltage category |
III
|
Product category |
Speed controller
|
Protocol |
PROFINET IO
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: for conducted emissions only |
Rated impulse withstand voltage (Uimp) |
2000 V
|
System configuration type |
Phase-earthed AC supply systems are not permitted.
AC voltage Center-point earthed star network (TN-S network) |
Mounting position |
Vertical
|
Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms, Half-sinusoidal shock 11 ms, 1000 shocks per shaft
|
Vibration |
Resistance: 10 - 150 Hz, Oscillation frequency
Resistance: 57 Hz, Amplitude transition frequency on acceleration Resistance: 6 Hz, Amplitude 0.15 mm Resistance: According to IEC/EN 60068-2-6 |
Altitude |
Above 1000 m with 1 % performance reduction per 100 m
Max. 2000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
< 95 %, no condensation
In accordance with IEC/EN 50178 |
Current limitation |
0.8 - 8.5 A, motor, main circuit
Adjustable, motor, main circuit |
Delay time |
< 10 ms, On-delay
< 10 ms, Off-delay |
Efficiency |
98 % (η)
|
Input current ILN at 150% overload |
7.8 A
|
Leakage current at ground IPE - max |
3.5 mA
|
Mains current distortion |
120 %
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
480 V
|
Mains voltage tolerance |
380 - 480 V (-10 %/+10 %, at 50/60 Hz)
|
Operating mode |
Sensorless vector control (SLV)
PM and LSPM motors U/f control Synchronous reluctance motors BLDC motors |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Overload current |
For 60 s every 600 s
At 40 °C |
Overload current IL at 150% overload |
12.7 A
|
Rated frequency - min |
45 Hz
|
Rated frequency - max |
66 Hz
|
Rated operational current (Ie) |
8.5 A at 150% overload (at an operating frequency of 8 kHz and an ambient air temperature of +40 °C)
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
0.75 kW
|
Rated operational voltage |
480 V AC, 3-phase
400 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable, fPWM, Power section, Main circuit
|
System configuration type |
Phase-earthed AC supply systems are not permitted.
AC voltage Center-point earthed star network (TN-S network) |
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
5 HP
|
Braking current |
≤ 0.6 A (max. 6 A for 120 ms), Actuator for external motor brake
|
Braking torque |
≤ 30 % (I/Ie)
Adjustable to 100 % (I/Ie), DC - Main circuit |
Braking voltage |
400/480 V AC -15 % / +10 %, Actuator for external motor brake
|
Switch-on threshold for the braking transistor |
765 VDC
|
Rated conditional short-circuit current (Iq) |
10 kA
|
Short-circuit protection (external output circuits) |
Type 1 coordination via the power bus' feeder unit, Main circuit
|
Rated control voltage (Uc) |
24 V DC (-15 %/+20 %, external via AS-Interface® plug)
400/480 V AC (external brake 50/60 Hz) |
Communication interface |
PROFINET, optional
|
Connection |
Plug type: HAN Q4/2
|
Interfaces |
Number of slave addresses: 31 (AS-Interface®)
Specification: S-7.4 (AS-Interface®) Max. total power consumption from AS-Interface® power supply unit (30 V): 250 mA |
Cable length |
C1 ≤ 1 m, maximum motor cable length
C3 ≤ 25 m, maximum motor cable length C2 ≤ 5 m, maximum motor cable length |
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|