Eaton DC1 Variable frequency drive, 230 V AC, 3-phase, 18 A, 4 kW, IP66/NEMA 4X, Radio interference suppression filter, Brake chopper, 7-digital display assembly, Local controls, Additional PCB protection, UV resistant, FS3
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
199422
|
EAN |
4015081978113
|
Product Length/Depth |
238 mm
|
Product Height |
310 mm
|
Product Width |
210.5 mm
|
Product Weight |
7 kg
|
Certifications |
RCM
UkrSEPRO Certified by UL for use in Canada CUL RoHS, ISO 9001 CE marking UL Listed IEC/EN 61800-2 CE UL report applies to both US and Canada UL 508C UL Category Control No.: NMMS, NMMS7 IEC/EN 61800-3 CSA-C22.2 No. 14 IEC/EN61800-5 UL EAC UL File No.: E172143 IEC/EN 61800-5-1 |
Catalog Notes |
|
Model Code |
DC1-32018FB-A6SOE1
|
Features |
Parameterization: drivesConnect
Parameterization: Fieldbus Parameterization: drivesConnect mobile (App) Parameterization: Keypad |
Fitted with: |
PC connection
Radio interference suppression filter Additional PCB protection Breaking resistance 7-digital display assembly Brake chopper Local controls Control unit Internal DC link IGBT inverter UV resistance |
Functions |
4-quadrant operation possible
|
Cable length |
C3 ≤ 25 m, maximum motor cable length
100 m, screened, maximum permissible cable length 200 m, screened, with motor choke, maximum permissible cable length 150 m, unscreened, maximum permissible cable length C2 ≤ 5 m, maximum motor cable length 300 m, unscreened, with motor choke, maximum permissible, Motor feeder |
Communication interface |
SmartWire-DT, optional
CANopen®, built in Modbus RTU, built in OP-Bus (RS485), built in |
Connection to SmartWire-DT |
No
|
Degree of protection |
IP66
NEMA 4X |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Frame size |
FS3
|
Mounting position |
Vertical
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
MODBUS
EtherNet/IP Other bus systems CAN |
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Suitable for |
Branch circuits, (UL/CSA)
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m |
Ambient operating temperature - min |
-20 °C
|
Ambient operating temperature - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
97 % (η)
|
Input current ILN at 150% overload |
20.9 A
|
Leakage current at ground IPE - max |
6.8 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
200 V
|
Mains voltage - max |
240 V
|
Operating mode |
Synchronous reluctance motors
Speed control with slip compensation PM motors Sensorless vector control (SLV) U/f control BLDC motors |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
230 V AC, 3-phase
240 V AC, 3-phase |
Overload current IL at 150% overload |
27 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) |
18 A at 150% overload (at an operating frequency of 6 kHz and an ambient air temperature of +40 °C)
|
Rated operational power at 220/230 V, 50 Hz, 3-phase |
4 kW
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
0.75 kW
|
Rated operational voltage |
240 V AC, 3-phase
230 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
20 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
175 % IH
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 24 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
240 V
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
15.2 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
14.8 A
|
Apparent power at 230 V |
7.17 kVA
|
Apparent power at 240 V |
7.48 kVA
|
Braking resistance |
25 Ω
|
Braking torque |
Max. 100 % of rated operational current Ie, variable, DC - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Max. 30 % MN, Standard - Main circuit |
Switch-on threshold for the braking transistor |
390 VDC
|
Number of inputs (analog) |
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
|
Number of inputs (digital) |
4 (parameterizable, 10 - 30 V DC)
|
Number of outputs (analog) |
1
|
Number of outputs (digital) |
1
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|