Ladda ner dokument () av 20

104612
Modellkod: NZM1-4-XFI30U

Eaton Moeller series NZM Earth-fault release, 30mA, 4p, bottom

General specifications

Product Name
Eaton Moeller series NZM Earth leakage relay
Catalog Number
104612
EAN
4015081044221
Product Length/Depth
180 mm
Product Height
80 mm
Product Width
120 mm
Product Weight
0.9 kg
Compliances
IEC
RoHS conform
Certifications
IEC/EN 60947-2 annex B
IEC/EN 60947-2
Model Code
NZM1-4-XFI30U

Tekniska data – elektriska

Application
In three-phase systems
Type
Accessory Earth-fault releases
Number of poles
Four-pole
Special features
Earth-fault release to IEC/EN 60947-2 Not UL/CSA approved Suitable for use in three-phase systems Pulse-current sensitive type A according to core-balance principle For 4 pole NZM1-4 circuit-breakers and N1-4 switch-disconnectors Supply voltage-dependent Ue = 200 – 415 V 50/60 Hz Control knobs, sealable. Bottom mounting up to 100 A
Frame
45 mm
NZM1
Used with
Four-pole
N1-4
NZM1-4

Tekniska data – elektriska

Rated control supply voltage (Us) at AC, 50 Hz - min
200 V
Rated control supply voltage (Us) at AC, 50 Hz - max
415 V
Rated control supply voltage (Us) at AC, 60 Hz - min
200 V
Rated control supply voltage (Us) at AC, 60 Hz - max
415 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Current rating - min
15 A
Current rating - max
100 A
Rated fault current - min
0.03 A
Rated fault current - max
0.03 A
Fault current detection range
50/60 Hz
Frequency rating
50 Hz / 60 Hz
Power on-delay time - min
30 ms
Power on-delay time - max
30 ms

Tekniska data – kommunikation

Sensitivity type
Pulse-current sensitive as per core-balance principle (type A)
Voltage rating
200 - 415 V AC, min. 80 V AC for detection of fault currents type A/AC (dependent on mains voltage)
Rated operating voltage (Ue) - max
415 V
Rated control supply voltage (Us) at AC, 50 Hz - min
200 V
Rated control supply voltage (Us) at AC, 50 Hz - max
415 V
Rated control supply voltage (Us) at AC, 60 Hz - min
200 V
Rated control supply voltage (Us) at AC, 60 Hz - max
415 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Current rating - min
15 A
Current rating - max
100 A
Rated fault current - min
0.03 A
Rated fault current - max
0.03 A
Fault current detection range
50/60 Hz
Frequency rating
50 Hz / 60 Hz
Power on-delay time - min
30 ms
Power on-delay time - max
30 ms

Tekniska data – mekaniska

Mounting Method
Bottom
Mounting position
Vertical and 90° in all directions
Degree of protection
IP20 (operating component area)
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Lifespan, mechanical
20000 operations

Exportera produktspecifikationer