General specifications

Product Name
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
Catalog Number
113025
EAN
4015081125654
Product Length/Depth
184 mm
Product Height
149 mm
Product Width
105 mm
Product Weight
2.623 kg
Compliances
RoHS conform
Certifications
UL489
CSA certified
Specially designed for North America
IEC60947-2
CE marking
CSA-C22.2 No. 5-09
UL listed
DIVQ
CSA (Class No. 1432-01)
UL (File No. E31593)
CSA (File No. 22086)
Model Code
NZMB2-A100-KCU-NA

Tekniska data – elektriska

Application
Feeder circuits, branch circuits
Number of poles
Three-pole
Features
Motor drive optional
Protection unit

Tekniska data – elektriska

Amperage Rating
100 A
Instantaneous current setting (Ii) - min
80 A
Instantaneous current setting (Ii) - max
100 A
Overload current setting (Ir) - min
80 A
Overload current setting (Ir) - max
100 A
Short delay current setting (Isd) - min
0 A
Short delay current setting (Isd) - max
0 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
25 kA
Electrical connection type of main circuit
Other
Handle type
Rocker lever

Tekniska data – kommunikation

Voltage rating
440 V - 440 V
Rated operating voltage Ue (UL) - max
600Y/347 V, 480 V
Amperage Rating
100 A
Instantaneous current setting (Ii) - min
80 A
Instantaneous current setting (Ii) - max
100 A
Overload current setting (Ir) - min
80 A
Overload current setting (Ir) - max
100 A
Short delay current setting (Isd) - min
0 A
Short delay current setting (Isd) - max
0 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
25 kA
Electrical connection type of main circuit
Other
Handle type
Rocker lever

Tekniska data – mekaniska

Mounting Method
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique
Degree of protection
IP20
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Position of connection for main current circuit
Front side

Exportera produktspecifikationer

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Authenticate Product

Enter your 16-17 digit serial number
The serial number you entered should not contain special charachter. The serial number you entered is not correct it should be of 16 or 17 digit. The serial number you entered was not found. Please try again or report this issue for further assistance. The serial number you entered does not match the product. Check your product's serial number and try again. Click here to navigate to the product page for the serial number you have entered The serial number is known to Eaton to be suspect, please try again or report this issue for further assistance..
Serial number
Reset The serial number is known to Eaton to be suspect, please try again or report this issue for further assistance. The Serial Number is not recognised by Eaton and is invalid. Please use this form to report this issue for further assistance..
Enter the 6 digit authentication code
The product you entered is suspect! Please try again or report this issue for further assistance. The authentication code you enter does not match our records for this serial number. Please try again, or report this issue for further assistance. Invalid Authentication code. Length must be 6 characters report this issue for further assistance. Authentication code is required report this issue for further assistance.
Complete Captcha challenge before authenticating.
Contact us to report-issue
x
Report an Issue
Please enter your full name.
x
Thank you, your issue has been submitted, our product team will contact with you soon.
Observera: Om fil(er) saknas från .zip nedladdningen stöds filtypen inte av massnedladdning.