Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Switch-disconnector 4p 1600A 1000VDC
Product Name |
Eaton Moeller series NZM switch-disconnector
|
Catalog Number |
152552
|
EAN |
4015081492985
|
Product Length/Depth |
401 mm
|
Product Height |
207 mm
|
Product Width |
280 mm
|
Product Weight |
22 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC
|
Model Code |
N4-4-1600-S1-DC
|
Application |
Open areas
Utility buildings
|
Type |
DC switch-disconnector
Switch-disconnector
|
Circuit breaker frame type |
N4
|
Number of poles |
Four-pole
|
Features |
Version as emergency stop installation
Motor drive optional Version as main switch Version as maintenance-/service switch Remote operation with shunt releases / remote operator |
Special features |
IEC/EN 60947-3
CCC China Compulsory Certificate
Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
N switch-disconnectors can be combined with NZM...-XU, NZM...-XA shunt releases and auxiliary contacts as well as with NZM...-XR... remote operator.
For DC switching, all 4 contacts must be connected in series. Refer to the information on jumper kit accessories.
Supplied as standard: Screw connection
box terminal optional.
When working with ungrounded systems (e.g., IT), the installation must ensure that a double ground fault will be impossible.
Switch can not be combined with plug-in/withdrawable units and/or connection on rear.
N4-4-...-S15-DC feeder unit and outgoer from the bottom only.
Lifespan, mechanical: of which max. 50 % trip by shunt/undervoltage release
Rated current = rated uninterrupted current: 1600 A
Values for rated uninterrupted current at 65 °C include jumpers.
|
Rated operating voltage (Ue) at AC - max |
0 V
|
Rated operating power at AC-23, 400 V |
0 kW
|
Current rating (Iu) at 40°C with terminal jumpers |
1600 A
|
Current rating (Iu) at 65°C with terminal jumpers |
1500 A
|
Rated operational current |
1400 CSA (DC-21B)
1600 A (DC 22-A) |
Rated permanent current at AC-21, 400 V |
0 A
|
Rated short-time withstand current (Icw) |
34 kA
|
Rated short-time withstand current (t = 0.1 s) |
34 kA
|
Amperage Rating |
1600 A
|
Rated operating power at AC-3, 400 V |
0 kW
|
Rated operating power at AC-23, 400 V |
0 kW
|
Switching power at 400 V |
0 kW
|
Electrical connection type of main circuit |
Screw connection
|
Number of operations per hour - max |
60
|
Handle type |
Rocker lever
|
Utilization category |
DC-22 A
|
Overvoltage category |
III
|
Pollution degree |
3
|
Voltage rating |
1000 V - 1000 V
|
Rated insulation voltage (Ui) |
1250 V
|
Current rating (Iu) at 40°C with terminal jumpers |
1600 A
|
Current rating (Iu) at 65°C with terminal jumpers |
1500 A
|
Rated operational current |
1400 CSA (DC-21B)
1600 A (DC 22-A) |
Rated permanent current at AC-21, 400 V |
0 A
|
Rated permanent current at AC-21, 400 V |
0 A
|
Rated conditional short-circuit current (Iq) |
0 kA
|
Rated short-time withstand current (Icw) |
34 kA
|
Rated short-time withstand current (t = 0.1 s) |
34 kA
|
Amperage Rating |
1600 A
|
Rated operating power at AC-3, 400 V |
0 kW
|
Rated operating power at AC-23, 400 V |
0 kW
|
Switching power at 400 V |
0 kW
|
Electrical connection type of main circuit |
Screw connection
|
Number of operations per hour - max |
60
|
Handle type |
Rocker lever
|
Utilization category |
DC-22 A
|
Overvoltage category |
III
|
Pollution degree |
3
|
Mounting Method |
Distribution board installation
Fixed Ground mounting Intermediate mounting Built-in device fixed built-in technique |
Degree of protection |
IP20
|
Degree of protection (IP), front side |
IP20
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Number of switches |
1
|
Handle color |
Black
|
Switch positions |
I, +, 0
|
Lifespan, mechanical |
10000 operations
|