Bilden är representativ
Download
Eaton Moeller series NZM Undervoltage release, 480-525VAC, for NZM2/3
| Product Name |
Eaton Moeller series NZM Undervoltage release
|
| Catalog Number |
259503
|
| EAN |
4015082595036
|
| Product Length/Depth |
42 mm
|
| Product Height |
90 mm
|
| Product Width |
30 mm
|
| Product Weight |
0.064 kg
|
| Compliances |
IEC
UL/CSA RoHS conform |
| Certifications |
CE marking
CSA certified CSA (Class No. 1437-01) UL489 CSA-C22.2 No. 5-09 IEC60947 UL listed CSA (File No. 22086) UL (File No. E140305) UL (Category Control Number DIHS) |
| Model Code |
NZM2/3-XU480-525AC
|
| Type |
Accessory
Undervoltage release
|
| Special features |
Non-delayed disconnection of NZM circuit-breaker or N switch-disconnector when the control voltage sinks below 35 – 70% US.
For use with emergency-stop devices in connection with an emergency-stop button.
When the under-voltage trip is switched off, accidental contact with the circuit breaker’s primary contacts is prevented when switched on.
Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
|
| Frame |
NZM2/3
|
| Suitable for |
Off-load switch
|
| Used with |
NZM3(-4), N(S)3(-4)
NZM2(-4), N(S)2(-4) |
| Rated control supply voltage |
480 - 525 V 50/60 Hz
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
480 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
525 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
480 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
525 V
|
| Rated control supply voltage (Us) at DC - min |
0 V
|
| Rated control supply voltage (Us) at DC - max |
0 V
|
| Voltage tolerance - min |
0.85
|
| Voltage tolerance - max |
1.1
|
| Drop-out voltage of undervoltage release AC/DC - min |
0.35 x Us
|
| Drop-out voltage of undervoltage release AC/DC - max |
0.7 x Us
|
| Power consumption |
0.8 W (sealing DC)
1.5 VA (sealing AC) |
| Pick-up power consumption at AC (undervoltage release) |
1.5 VA
|
| Pick-up power consumption at DC (undervoltage release) |
0.8 W
|
| Reaction time |
19 ms
|
| Minimum command time - min |
10 ms
|
| Minimum command time - max |
15 ms
|
| Electric connection type |
Screw connection
|
| Voltage type |
AC
|
| Rated control voltage (relay contacts) |
480 V AC
525 V AC |
| Rated control supply voltage |
480 - 525 V 50/60 Hz
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
480 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
525 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
480 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
525 V
|
| Rated control supply voltage (Us) at DC - min |
0 V
|
| Rated control supply voltage (Us) at DC - max |
0 V
|
| Voltage tolerance - min |
0.85
|
| Voltage tolerance - max |
1.1
|
| Drop-out voltage of undervoltage release AC/DC - min |
0.35 x Us
|
| Drop-out voltage of undervoltage release AC/DC - max |
0.7 x Us
|
| Power consumption |
0.8 W (sealing DC)
1.5 VA (sealing AC) |
| Pick-up power consumption at AC (undervoltage release) |
1.5 VA
|
| Pick-up power consumption at DC (undervoltage release) |
0.8 W
|
| Reaction time |
19 ms
|
| Minimum command time - min |
10 ms
|
| Minimum command time - max |
15 ms
|
| Electric connection type |
Screw connection
|
| Number of contacts (change-over contacts) |
0
|
| Number of contacts (normally closed contacts) |
0
|
| Number of contacts (normally open contacts) |
0
|
| Connection type |
With bolt connection
|