266017
Modellkod: PN3-400

Eaton Moeller series NZM - Molded Case Circuit Breaker. Switch-disconnector 3p, 400A

General specifications

Product Name
Eaton Moeller series NZM - Molded case circuit breaker
Catalog Number
266017
EL Number
3186819
EAN
4015082660178
Product Length/Depth
159 mm
Product Height
275 mm
Product Width
140 mm
Product Weight
4.795 kg
Compliances
RoHS conform
Certifications
IEC/EN 60947
IEC
Model Code
PN3-400

Tekniska data – elektriska

Application
Use in unearthed supply systems at 690 V
Type
Switch-disconnector
Circuit breaker frame type
PN3
Number of poles
Three-pole
Features
Version as main switch
Version as maintenance-/service switch
Version as emergency stop installation
Special features
  • Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
  • Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
  • Busbar tag shroud to VDE 0160 Part 100.
  • Rated current = rated uninterrupted current: 400 A

Tekniska data – elektriska

Rated operating voltage (Ue) at AC - max
690 V
Rated operating power at AC-23, 400 V
200 kW
Rated operational current
630 A (415 V AC-22/23A, making and breaking capacity)
630 A (690 V AC-22/23A, making and breaking capacity)
Rated conditional short-circuit current with back-up fuse
PN3(N3)-400…630: 630 AgGgL
100 kA at 400/415 V
80 kA at 690 V
Rated conditional short-circuit current with downstream fuse
PN3(N3)-400…630: 630 AgGgL
100 kA at 400/415 V
80 kA at 690 V
Rated short-time withstand current (Icw)
12 kA
Rated short-time withstand current (t = 0.3 s)
12 kA
Rated short-time withstand current (t = 1 s)
12 kA
Amperage Rating
400 A
Rated operating frequency
50 Hz
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
25 kA
Rated operating power at AC-23, 400 V
200 kW
Short-circuit protective device fuses - max
630 A gL
Electrical connection type of main circuit
Screw connection
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Number of operations per hour - max
60
Handle type
Rocker lever
Overvoltage category
III
Pollution degree
3
Lifespan, electrical
3000 operations at 400 V AC-3
2000 operations at 690 V AC-3
3000 operations at 690 V AC-1
5000 operations at 415 V AC-1
3000 operations at 415 V AC-3
5000 operations at 400 V AC-1
Direction of incoming supply
As required

Tekniska data – kommunikation

Voltage rating
690 V - 690 V
Rated insulation voltage (Ui)
1000 V
Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated operational current
630 A (415 V AC-22/23A, making and breaking capacity)
630 A (690 V AC-22/23A, making and breaking capacity)
Rated conditional short-circuit current with back-up fuse
PN3(N3)-400…630: 630 AgGgL
100 kA at 400/415 V
80 kA at 690 V
Rated conditional short-circuit current with downstream fuse
PN3(N3)-400…630: 630 AgGgL
100 kA at 400/415 V
80 kA at 690 V
Rated short-time withstand current (Icw)
12 kA
Rated short-time withstand current (t = 0.3 s)
12 kA
Rated short-time withstand current (t = 1 s)
12 kA
Amperage Rating
400 A
Rated operating frequency
50 Hz
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
25 kA
Rated operating power at AC-23, 400 V
200 kW
Short-circuit protective device fuses - max
630 A gL
Electrical connection type of main circuit
Screw connection
Isolation
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts)
Number of operations per hour - max
60
Handle type
Rocker lever
Overvoltage category
III
Pollution degree
3
Lifespan, electrical
3000 operations at 400 V AC-3
2000 operations at 690 V AC-3
3000 operations at 690 V AC-1
5000 operations at 415 V AC-1
3000 operations at 415 V AC-3
5000 operations at 400 V AC-1
Direction of incoming supply
As required

Tekniska data – mekaniska

Mounting Method
Ground mounting
Fixed
Built-in device fixed built-in technique
Distribution board installation
Intermediate mounting
Degree of protection
IP20 (basic protection type, in the area of the HMI devices)
Other
Degree of protection (IP), front side
IP20
IP40 (with insulating surround)
IP66 (with door coupling rotary handle)
Degree of protection (terminations)
IP10 (tunnel terminal)
IP00 (terminations, phase isolator and band terminal)
Protection against direct contact
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Number of switches
1
Handle color
Black
Switch positions
I, 0
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Lifespan, mechanical
15000 operations

Exportera produktspecifikationer

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Autentisera produkten

Ange ditt serienummer med 16–17 siffror
Det angivna serienumret får inte innehålla specialtecken. Det angivna serienumret är inte korrekt. Det ska bestå av 16 eller 17 siffror. Det angivna serienumret hittades inte. Försök igen eller rapportera ett problem för ytterligare hjälp. Det angivna serienumret matchar inte produkten. Kontrollera produktens serienummer och försök igen. Klicka här för att navigera till produktsidan för serienumret du angett Eaton känner till att serienumret är misstänkt, försök igen eller rapportera ett problem för ytterligare hjälp.
Serienummer
Återställ Eaton känner till att serienumret är misstänkt, försök igen eller rapportera ett problem för ytterligare hjälp. Serienumret känns inte igen av Eaton och är ogiltigt. Använd detta formulär för att rapportera ett problem för ytterligare hjälp.
Ange den 6-siffriga autentiseringskoden
Den angivna produkten är misstänkt! Försök igen eller rapportera ett problem för ytterligare hjälp. Den angivna autentiseringskoden matchar inte våra register för detta serienummer. Försök igen eller rapportera ett problem för ytterligare hjälp. Ogiltig autentiseringskod. Längden måste vara 6 tecken rapportera ett problem för ytterligare hjälp. Autentiseringskod krävs rapportera ett problem för ytterligare hjälp.
Slutföra Captcha-utmaningen före autentiseringen.
Kontakta oss rapportera problem
x
Rapportera ett problem
Ange ditt fullständiga namn.
x
Tack, ditt ärende har skickats in. Vårt produktteam ska kontakta dig snart!
Observera: Om fil(er) saknas från .zip nedladdningen stöds filtypen inte av massnedladdning.