Eaton Moeller® series DILK Contactor for capacitors, with series resistors, 12.5 kVAr, 415 V 50 Hz, 480 V 60 Hz
Product Name |
Eaton Moeller® series DILK capacity contactor
|
Catalog Number |
293991
|
EAN |
4015082939915
|
Product Length/Depth |
138 mm
|
Product Height |
135 mm
|
Product Width |
45 mm
|
Product Weight |
0.51 kg
|
Certifications |
CSA File No.: 012528
IEC/EN 60947-4-1 CSA-C22.2 No. 60947-4-1-14 UL File No.: E29096 IEC/EN 60947 CE UL CSA CSA Class No.: 3211-04 UL 60947-4-1 UL Category Control No.: NLDX |
Model Code |
DILK12-11(415V50HZ,480V60HZ)
|
Fitted with: |
Series resistors
|
Application |
Contactors for power factor correction
|
Connection |
Screw terminals
|
Lifespan, electrical |
150,000 Operations
|
Operating frequency |
120 Operations/h
|
Product category |
DILK Contactors for capacitors
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Voltage type |
AC
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Emitted interference |
According to EN 60947-1
|
Interference immunity |
According to EN 60947-1
|
Terminal capacity (flexible with ferrule) |
1 x (0.75 - 16) mm², Main cables
|
Terminal capacity (solid) |
1 x (0.75 - 16) mm², Main cables
|
Terminal capacity (solid/stranded AWG) |
18 - 6, Main cables
|
Terminal capacity (stranded) |
1 x 16 mm², Main cables
|
Rated operational power at AC-6B, 220/230 V, 50 Hz |
7.5 kVA
|
Rated operational power at AC-6B, 380/400 V, 50 Hz |
12.5 kVA
|
Rated operational power at AC-6B, 525 V, 50 Hz |
16.7 kVA
|
Rated operational power at AC-6B, 690 V, 50 Hz |
20 kVA
|
Switching capacity (auxiliary contacts, general use) |
10 A, 600 V AC, (UL/CSA)
1 A, 250 V DC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) |
A600, AC operated (UL/CSA)
P300, DC operated (UL/CSA) |
Arcing time |
10 ms
|
Drop-out voltage |
AC operated: 0.6 - 0.3 x UC, AC operated
|
Duty factor |
100 %
|
Pick-up voltage |
0.8 - 1.1 V AC x Uc
|
Power consumption, pick-up, 50 Hz |
58 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
|
Power consumption, pick-up, 60 Hz |
71 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
|
Power consumption, sealing, 50 Hz |
7.6 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
Power consumption, sealing, 60 Hz |
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
9.3 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
Rated control supply voltage (Us) at AC, 50 Hz - min |
415 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
415 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
480 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
480 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Switching time (AC operated, make contacts, closing delay) - min |
16 ms
|
Switching time (AC operated, make contacts, closing delay) - max |
22 ms
|
Switching time (AC operated, make contacts, opening delay) - min |
8 ms
|
Switching time (AC operated, make contacts, opening delay) - max |
14 ms
|
Making capacity without damping (I-peak value) |
180 x Ie
|
Number of auxiliary contacts (normally closed contacts) |
1
|
Number of auxiliary contacts (normally open contacts) |
1
|
Special purpose rating of capacitor switching |
18 A, 240 V 60 Hz 3phase, (UL/CSA)
18 A, 480 V 60 Hz 3phase, (UL/CSA) 15 kVar, 480 V 60 Hz 3phase, (UL/CSA) 15 kVar, 600 V 60 Hz 3phase, (UL/CSA) 7.5 kVar, 240 V 60 Hz 3phase, (UL/CSA) 14.4 A, 600 V 60 Hz 3phase, (UL/CSA) |
Equipment heat dissipation, current-dependent Pvid |
2.1 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0.7 W
|
Rated operational current for specified heat dissipation (In) |
18 A
|
Static heat dissipation, non-current-dependent Pvs |
2.1 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|