Eaton DA1 Frequency inverter, 400 V AC, 3-phase, 72 A, 37 kW, IP20/NEMA 0, Radio interference suppression filter, Additional PCB protection, DC link choke, FS5
Product Name |
Eaton DA1 Variable frequency drive
|
Catalog Number |
197497
|
EAN |
4015081940721
|
Product Length/Depth |
261 mm
|
Product Height |
485 mm
|
Product Width |
234 mm
|
Product Weight |
18.2 kg
|
Certifications |
CE
IEC/EN61800-5 IEC/EN 61800-3 RoHS, ISO 9001 Certified by UL for use in Canada EAC RCM UkrSEPRO UL UL Category Control No.: NMMS, NMMS7 UL File No.: E172143 IEC/EN 61800-2 Safety: EN 61800-5-1: 2003 UL report applies to both US and Canada UL 508C CUL IEC/EN61800-3 |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Model Code |
DA1-34072FB-B20C
|
Cable length |
100 m, screened, maximum permissible cable length
C3 ≤ 25 m, maximum motor cable length C2 ≤ 5 m, maximum motor cable length 200 m, screened, with motor choke, maximum permissible cable length 200 m, unscreened, with motor choke, maximum permissible cable length 150 m, unscreened, maximum permissible cable length |
Communication interface |
Modbus RTU
DeviceNet, optional Ethernet IP, optional PROFIBUS, optional EtherCAT, optional CANopen® PROFINET, optional Modbus-TCP, optional SmartWire-DT, optional OP-Bus (RS485) |
Connection to SmartWire-DT |
Yes
In conjunction with DX-NET-SWD1 SmartWire DT module |
Degree of protection |
IP20
NEMA Other |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Fitted with: |
Radio interference suppression filter
Additional PCB protection DC link choke Internal DC link Control unit OLED display Brake chopper IGBT inverter PC connection Breaking resistance |
Frame size |
FS5
|
Functions |
4-quadrant operation possible
|
Mounting position |
Vertical
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
CAN
Other bus systems DeviceNet TCP/IP EtherNet/IP MODBUS PROFINET IO PROFIBUS |
Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
Suitable for |
Branch circuits, (UL/CSA)
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 1000 m Max. 4000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
97.2 % (η)
|
Heat dissipation at current/speed |
1050 W at 100% current and 90% speed
310 W at 25% current and 0% speed 310 W at 25% current and 50% speed 370 W at 50% current and 0% speed 460 W at 50% current and 50% speed 530 W at 50% current and 90% speed 720 W at 100% current and 0% speed 930 W at 100% current and 50% speed |
Input current ILN at 150% overload |
76.4 A
|
Leakage current at ground IPE - max |
0.49 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
480 V
|
Operating mode |
U/f control
Optional: Vector control with feedback (CLV) Speed control with slip compensation Sensorless vector control (SLV) |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
480 V AC, 3-phase
400 V AC, 3-phase |
Overload current IL at 150% overload |
105 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) at 150% overload |
72 A
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
37 kW
|
Rated operational voltage |
480 V AC, 3-phase
400 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Starting current - max |
200 %, IH, max. starting current (High Overload), for 4 seconds every 40 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 24 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
480 VAC
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
72 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
65 A
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
50 HP
|
Apparent power at 400 V |
49.88 kVA
|
Apparent power at 480 V |
59.86 kVA
|
Braking resistance |
12 Ω
|
Braking torque |
Adjustable to 100 % (DC)
Max. 30 % MN, Standard - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Switch-on threshold for the braking transistor |
780 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
5
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
2
|
Number of relay outputs |
2 (parameterizable, 1 N/O and 1 changeover contact, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA)
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|