Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 4p, 125A, B, frame2, 4-A125
| Product Name |
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
|
| Catalog Number |
265847
|
| EAN |
4015082658472
|
| Product Length/Depth |
149 mm
|
| Product Height |
184 mm
|
| Product Width |
140 mm
|
| Product Weight |
3 kg
|
| Compliances |
RoHS conform
|
| Certifications |
IEC/EN 60947
|
| Model Code |
NZMB2-4-A125
|
| Application |
Use in unearthed supply systems at 440 V
|
| Number of poles |
Four-pole
|
| Features |
Protection unit
Motor drive optional |
| Special features |
|
| Current rating of neutral conductor |
200% of phase conductor
|
| Amperage Rating |
125 A
|
| Instantaneous current setting (Ii) - min |
6 A
|
| Instantaneous current setting (Ii) - max |
10 A
|
| Overload current setting (Ir) |
100 A - 125 A
|
| Overload current setting (Ir) - min |
100 A
|
| Overload current setting (Ir) - max |
125 A
|
| Short-circuit release non-delayed setting - min |
750 A
|
| Short-circuit release non-delayed setting - max |
1250 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
| Electrical connection type of main circuit |
Screw connection
|
| Isolation |
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts) |
| Handle type |
Rocker lever
|
| Voltage rating |
440 V - 440 V
|
| Current rating of neutral conductor |
200% of phase conductor
|
| Amperage Rating |
125 A
|
| Instantaneous current setting (Ii) - min |
6 A
|
| Instantaneous current setting (Ii) - max |
10 A
|
| Overload current setting (Ir) |
100 A - 125 A
|
| Overload current setting (Ir) - min |
100 A
|
| Overload current setting (Ir) - max |
125 A
|
| Short-circuit release non-delayed setting - min |
750 A
|
| Short-circuit release non-delayed setting - max |
1250 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
| Electrical connection type of main circuit |
Screw connection
|
| Isolation |
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts) |
| Handle type |
Rocker lever
|
| Mounting Method |
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional Fixed |
| Degree of protection |
IP20
|
| Protection against direct contact |
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
|
| Number of auxiliary contacts (change-over contacts) |
0
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Number of auxiliary contacts (normally open contacts) |
0
|
| Position of connection for main current circuit |
Front side
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |