Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 63A, B, frame1, A63-NA
Product Name |
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
|
Catalog Number |
272255
|
EAN |
4015082722555
|
Product Length/Depth |
88 mm
|
Product Height |
165.5 mm
|
Product Width |
90 mm
|
Product Weight |
1.073 kg
|
Compliances |
RoHS conform
|
Certifications |
CSA-C22.2 No. 5-09
UL (File No. E31593) CE marking UL 489 UL (Category Control Number DIVQ) IEC 60947-2 CSA (File No. 22086) IEC CSA (Class No. 1432-01) CSA certified IEC/EN 60947 UL listed Specially designed for North America UL/CSA |
Model Code |
NZMB1-A63-NA
|
Application |
|
Type |
Circuit breaker
|
Circuit breaker frame type |
NZM1
|
Number of poles |
Three-pole
|
Release system |
Thermomagnetic release
|
Features |
Protection unit
|
Special features |
|
Rated operational current |
160 A (380/400 V AC-1, making and breaking capacity)
125 A (415 V AC-1, making and breaking capacity) |
Amperage Rating |
63 A
|
Instantaneous current setting (Ii) - min |
380 A
|
Instantaneous current setting (Ii) - max |
630 A
|
Overload current setting (Ir) - min |
50 A
|
Overload current setting (Ir) - max |
63 A
|
Short delay current setting (Isd) - min |
0 A
|
Short delay current setting (Isd) - max |
0 A
|
Short-circuit release non-delayed setting - min |
378 A
|
Short-circuit release non-delayed setting - max |
630 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
30 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
18.5 kA
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
63 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
53 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
53 kA
|
Short-circuit total breaktime |
< 10 ms
|
Low-voltage HBC fuse - max |
200 A gG/gL
|
Electrical connection type of main circuit |
Frame clamp
|
Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
Number of operations per hour - max |
120
|
Handle type |
Rocker lever
|
Utilization category |
A (IEC/EN 60947-2)
|
Overvoltage category |
III
|
Pollution degree |
3
|
Lifespan, electrical |
7500 operations at 400 V AC-1
|
Direction of incoming supply |
As required
|
Voltage rating |
440 V - 440 V
|
Rated operating voltage Ue (UL) - max |
480 Y / 277 V
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
6000 V
|
Rated operational current |
160 A (380/400 V AC-1, making and breaking capacity)
125 A (415 V AC-1, making and breaking capacity) |
Amperage Rating |
63 A
|
Instantaneous current setting (Ii) - min |
380 A
|
Instantaneous current setting (Ii) - max |
630 A
|
Overload current setting (Ir) - min |
50 A
|
Overload current setting (Ir) - max |
63 A
|
Short delay current setting (Isd) - min |
0 A
|
Short delay current setting (Isd) - max |
0 A
|
Short-circuit release non-delayed setting - min |
378 A
|
Short-circuit release non-delayed setting - max |
630 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
30 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
18.5 kA
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
63 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
53 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
53 kA
|
Short-circuit total breaktime |
< 10 ms
|
Low-voltage HBC fuse - max |
200 A gG/gL
|
Electrical connection type of main circuit |
Frame clamp
|
Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
Number of operations per hour - max |
120
|
Handle type |
Rocker lever
|
Utilization category |
A (IEC/EN 60947-2)
|
Overvoltage category |
III
|
Pollution degree |
3
|
Lifespan, electrical |
7500 operations at 400 V AC-1
|
Direction of incoming supply |
As required
|
Mounting Method |
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional Fixed |
Degree of protection |
IP20 (basic degree of protection, in the operating controls area)
IP20 |
Degree of protection (IP), front side |
IP66 (with door coupling rotary handle)
IP40 (with insulating surround) |
Degree of protection (terminations) |
IP00 (terminations, phase isolator and strip terminal)
IP10 (tunnel terminal) |
Protection against direct contact |
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
|
Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Position of connection for main current circuit |
Front side
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Lifespan, mechanical |
20000 operations
|