Eaton Moeller series Power Defense - Molded Case Circuit Breaker. Switch-disconnector, 3 p, 63A, frame size 1
Product Name |
Eaton Moeller series Power Defense molded case switch-disconnector
|
Catalog Number |
111994
|
EAN |
4015081115426
|
Product Length/Depth |
88 mm
|
Product Height |
145 mm
|
Product Width |
90 mm
|
Product Weight |
0.926 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC
|
Model Code |
LN1-63-I
|
Circuit breaker frame type |
LN1
|
Application |
Use in unearthed supply systems at 690 V
|
Amperage Rating |
63 A
|
Number of poles |
Three-pole
|
Voltage rating |
690 V - 690 V
|
Rated operating voltage (Ue) at AC - max |
400 V
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
6000 V
|
Rated operational current |
160 A (415 V AC-22/23A, making and breaking capacity)
160 A (690 V AC-1, making and breaking capacity) 160 A (690 V AC-22/23A, making and breaking capacity) 160 A (415 V AC-1, making and breaking capacity) |
Rated conditional short-circuit current with back-up fuse |
80 kA at 690 V
PN1(N1)-63…125: 125 AgGgL; PN1(N1)-160: 160 AgGgL 100 kA at 400/415 V |
Rated conditional short-circuit current with downstream fuse |
100 kA at 400/415 V
10 kA at 690 V PN1(N1)-63…125: 125 AgGgL; PN1(N1)-160: 160 AgGgL |
Rated short-time withstand current (Icw) |
2 kA
|
Rated short-time withstand current (t = 0.3 s) |
2 kA
|
Rated short-time withstand current (t = 1 s) |
2 kA
|
Rated permanent current at AC-21, 400 V |
0 A
|
Rated operating frequency |
50 Hz
|
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz |
2.8 kA
|
Rated operating power at AC-3, 400 V |
0 kW
|
Rated operating power at AC-23, 400 V |
30 kW
|
Switching power at 400 V |
0 kW
|
Short-circuit total breaktime |
< 10 ms
|
Short-circuit protective device fuses - max |
125 A gL
|
Electrical connection type of main circuit |
Frame clamp
|
Overvoltage category |
III
|
Pollution degree |
3
|
Lifespan, electrical |
7500 operations at 400 V AC-3
10000 operations at 415 V AC-1 10000 operations at 400 V AC-1 5000 operations at 690 V AC-3 7500 operations at 415 V AC-3 7500 operations at 690 V AC-1 |
Type |
Switch-disconnector
|
Mounting Method |
Distribution board installation
Intermediate mounting Built-in device fixed built-in technique Ground mounting Fixed |
Degree of protection (IP), front side |
IP20
|
Switch positions |
I, +, 0
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Number of operations per hour - max |
120
|
Handle type |
Rocker lever
|
Handle color |
Gray
|
Standard terminals |
Box terminal
|
Terminal capacity (control cable) |
0.75 mm² - 2.5 mm² (1x)
0.75 mm² - 1.5 mm² (2x) |
Terminal capacity (aluminum solid conductor/cable) |
16 mm² (1x) at tunnel terminal
|
Terminal capacity (copper busbar) |
Min. 12 mm x 5 mm direct at switch rear-side connection
Max. 16 mm x 5 mm direct at switch rear-side connection M6 at rear-side screw connection |
Terminal capacity (copper solid conductor/cable) |
10 mm² - 16 mm² (1x) at box terminal
6 mm² - 16 mm² (2x) direct at switch rear-side connection 6 mm² - 16 mm² (2x) at box terminal 16 mm² (1x) at tunnel terminal 10 mm² - 16 mm² (1x) direct at switch rear-side connection |
Terminal capacity (copper stranded conductor/cable) |
25 mm² (2x) direct at switch rear-side connection
25 mm² - 70 mm² (1x) direct at switch rear-side connection 25 mm² - 70 mm² (1x) at box terminal 25 mm² (2x) at box terminal 25 mm² - 95 mm² (1x) at tunnel terminal |
Terminal capacity (copper strip) |
Max. 9 segments of 9 mm x 0.8 mm at box terminal
Min. 2 segments of 9 mm x 0.8 mm at box terminal |
Lifespan, mechanical |
20000 operations
|
Rated operational current for specified heat dissipation (In) |
63 A
|
Equipment heat dissipation, current-dependent |
4.52 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
Features |
Motor drive optional
Version as maintenance-/service switch Version as main switch |
Functions |
Voltage release optional
Disconnectors/main switches Interlockable |
Special features |
Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
Busbar tag shroud to VDE 0160 Part 100.
Rated current = rated uninterrupted current: 63 A
|