Eaton XIOC Communication module for XC100/200, 24 V DC, profibus-DP module
| Product Name |
Eaton XIOC Communication module
|
| Catalog Number |
286419
|
| EAN |
4015082864194
|
| Product Length/Depth |
100 mm
|
| Product Height |
95 mm
|
| Product Width |
30 mm
|
| Product Weight |
0.145 kg
|
| Certifications |
UL File No.: E135462
UL508 CSA-C22.2 No. 0-M IEC/EN 61131-2 CE CSA Class No.: 2252-01 UL Category Control No.: NRAQ CSA UL CSA File No.: 012528 CSA-C22.2 No. 142-M EN 50178 |
| Model Code |
XIOC-NET-DP-S
|
| Functions |
Slave
|
| Current consumption |
300 mA (Ie), Interfaces
300 mA, Interfaces |
| Degree of protection |
IP20
|
| Overvoltage category |
II
|
| Pollution degree |
2
|
| Protection class |
1
|
| Repetition rate |
1 s
|
| Residual ripple |
≤ 5 %
|
| Resistance |
500 g/⌀ 50 mm ±25 g (impact resistance)
|
| Type |
|
| Used with |
XC100/200 (expandable with up to 15 XI/OC modules)
|
| Shock resistance |
15 g, Mechanical, Shock duration 11 ms
|
| Vibration resistance |
10 - 57 Hz, ± 0.075 mm
57 - 150 Hz ± 1.0 mm |
| Ambient operating temperature - min |
0 °C
|
| Ambient operating temperature - max |
55 °C
|
| Ambient storage temperature - min |
-20 °C
|
| Ambient storage temperature - max |
70 °C
|
| Emitted interference |
Class A (according to DIN/EN 55011/22)
|
| Voltage dips |
10 ms
|
| Terminals |
Optionally, screw terminals or spring-loaded terminals for digital/analog modules
|
| Power loss |
7.2 W
|
| Rated operational voltage |
24 (12) V DC
|
| Supply voltage |
20.4 – 28.8 (11.8 – 14.4) V DC, Admissible range, Power supply
|
| Bus termination |
Switchable
|
| Data transfer rate |
6000 kBit/s with 100 m
187.5 kBit/s with 1000 m 500 kBit/s with 400 m Transmit/Receive data: 244 Bytes max. 93.75 kBit/s with 1200 m 9.6 - 12000 kBit/s 1500 kBit/s with 200 m 9.6 kBit/s with 1200 m 19.2 kBit/s with 1200 m 3000 kBit/s with 100 m 12000 kBit/s with 100 m |
| Interfaces |
PROFIBUS DP, RS485, EN 50170 (built-in)
|
| LED indicator |
Status indication of Bus diagnostics: LED
|
| Number of modules |
1 (XC100)
3 (XC200) |
| Number of slots |
3
|
| Plug type |
9-pole SUB-D socket
|
| Protocol |
PROFIBUS
|
| Explosion safety category for dust |
None
|
| Explosion safety category for gas |
None
|
| Potential isolation |
Interfaces: yes
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
7.2 W
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
Support from Eaton
Contact us
+359884477015