Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 33A, N2-S33-CNA
| Product Name |
Eaton Moeller series NZM molded case circuit breaker magnetic
|
| Catalog Number |
103045
|
| EAN |
4015081028849
|
| Product Length/Depth |
149 mm
|
| Product Height |
195 mm
|
| Product Width |
105 mm
|
| Product Weight |
2.345 kg
|
| Compliances |
RoHS conform
|
| Certifications |
UL (File No. E31593)
UL 489 Specially designed for North America UL (Category Control Number DKPU2) CSA (Class No. 1432-01) CSA (File No. 22086) UL listed CSA-C22.2 No. 5-09 UL/CSA CSA certified |
| Model Code |
NZMN2-S33-CNA
|
| Voltage rating |
690 V - 690 V
|
| Amperage Rating |
33 A
|
| Short-circuit total breaktime |
< 10 ms
|
| Electrical connection type of main circuit |
Screw connection
|
| Isolation |
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts) |
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Lifespan, electrical |
5000 operations at 690 V AC-3
6500 operations at 400 V AC-3 6500 operations at 415 V AC-3 10000 operations at 400 V AC-1 7500 operations at 690 V AC-1 |
| Direction of incoming supply |
As required
|
| Amperage Rating |
33 A
|
| Short-circuit total breaktime |
< 10 ms
|
| Electrical connection type of main circuit |
Screw connection
|
| Isolation |
500 V AC (between auxiliary contacts and main contacts)
300 V AC (between the auxiliary contacts) |
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Lifespan, electrical |
5000 operations at 690 V AC-3
6500 operations at 400 V AC-3 6500 operations at 415 V AC-3 10000 operations at 400 V AC-1 7500 operations at 690 V AC-1 |
| Direction of incoming supply |
As required
|
| Mounting Method |
Fixed
Built-in device fixed built-in technique DIN rail (top hat rail) mounting optional |
| Degree of protection |
IP20 (basic degree of protection, in the operating controls area)
IP20 |
| Degree of protection (IP), front side |
IP40 (with insulating surround)
IP66 (with door coupling rotary handle) |
| Degree of protection (terminations) |
IP00 (terminations, phase isolator and strip terminal)
IP10 (tunnel terminal) |
| Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
| Lifespan, mechanical |
20000 operations
|